The purpose of this RFQ is to hire a qualified electrical Contractor for electrical services for the installation of various pieces of equipment at the OMIC R&D Campus in Scappoose, OR. Contractors are to refer to document titled “Attachment A: Electrical for Titomic, Dust Collector, AirGas N2 Sytems”, plans for details, attached as Exhibit B. Oregon Tech is seeking for the following services to be provided: Building 2 – Additive Center, Titomic Cold Spray Installation 1. Titomic Enclosure: See Exhibit B, (Drawing number 1147-99-01-0). Exact location within the enclosure TBD by owner in the field. a. Power Supply : 120v, 1Ø 2 amp receptacle. b. Power Supply: 480v 3Ø Delta 13kVA receptacle. c. 2 X Power Supply: 480v, 90 amp receptacle. d. Power Supply: 400v 3Ø Wye 40 amp receptacle. e. Power Supply: 200v, 1Ø 15 amp receptacle. f. Power Supply: 120v, 1Ø 15 amp receptacle.