Specifications include, but are not limited to: a. Seven (7) - 12’x16’x10’h min outside Dimensions; b. Shelters shall meet all applicable local and state building codes, Motorola R56 Standards, or industry best standards, rules and regulation and have the Oregon Gold Seal stamp if required.; Note: the design shall recognize this shelter as an “essential facility” as defined in the 2019 Oregon Structural Specialty Code (OSSC) which is based on the 2013 IBC. Vendor shall submit an electronic copy of plans and specifications stamped by an Oregon registered structural engineer. Note: Vendor to provide wet stamped drawings if required by the permitting jurisdiction.; c. The shelter shall be designed with a 300lb per square foot floor loading capability (4’x4’ area to accommodate 7,000lb battery loading), and a 150lb per square foot roof loading capability or as required by the OSSC / IBC for the snow load at the particular site. Roof shall have a ¼” per foot slope and a 6” overhang on all sides.; Note: Provide an option for the addition of an A-frame type snow shedding roof to be placed on the structural roof at high snow locations.; d. The exterior finish shall be exposed aggregate.; e. Roof material shall be EPDM applied to structure per manufactures instructions with required brown anodized aluminum flashing materials.; f. The shelters shall provide 2-hour fire rating per OSSC/IBC, shall be weather tight including wind and moisture, (Note: snow may accumulate to and beyond the roof line at some sites) and shall require minimal maintenance.; g. The shelter shall have the following items: i. Exterior Door: 3’4” x 7' galvanized and painted steel.; 1. 3 non-corrosive / non-removable pin / 4.5”x4.5” hinges or a continuous hinge; 2. mortise lockset with deadbolt – Best Lock w/ construction core; 3. 6” Lock Guard; 4. aluminum threshold and door sweep; 5. weather stripping; 6. door drip cap; ii. 3’x 3’ Metal canopy over exterior door with a brown powder coat finish.; iii. Interior Finish: ¾” ACX Plywood w/ an undercoat and 2 coats of white epoxy paint on walls and ceiling. Paint equal to Sherman Williams Pro Industrial™ Pre-Catalyzed Water Based Epoxy egg shell finish.; iv. Insulation: Minimum R-22 walls and R-30 in ceiling.; v. Flooring: 1/8" vinyl floor tile and cove molding.