The goal of this solicitation is to secure a source to purchase a Blue Star Series MD800-01 Generator or Acceptable Equivalent for the Riverside Lift Station for the Water and Sewer Department of the City of Tulsa. Generator shall be as follows: • Blue Star Series MD800-01 or Acceptable Equivalent • Only Basler DGC2020 controllers will be accepted • Acceptable Equivalent shall be an American owned company • 800KW, 60 Hz, 277/480v, 3 phase 1200- amp 100% rated output breaker with lockout device, mounted in a NEMA 1 enclosure. • Stamford S6L1D-C 12 lead, re-connectablehigh wye • Brushless, single bearing • Direct connection to engine with flex plate • PMG- Generator • Class H insulation • Meets NEMA MG 1, IEEE, ANSI Standards Compliance for Temperature Rise and CSA standards • Wave form deviation factor no more than 5% • Harmonic content not more than 5% maximum • Self-ventilated, drip- proof construction • Automatic voltage regulator with: o Over excitation protection o Under frequency protection o EMI o Fully encapsulated o +/-1% voltage regulation; Stamford MX321 Automatic Voltage Regulator