MACHINE ROOM 1. Provide convenient GFCI outlets only. 2. Machine room door must be fire rated for 1.5hrs min. 3. 4. 5. 6, Machine room lighting must be a minimum of 19-foot candles. Confirm adequate room temperature/humidity as per elevator manufacture specifications. All wiring in machine room must be in conduit or flame-retardant and jacketed. Machine room must not be used as a chase way, Only elevator equipment and wiring allowed. Remove or separate plumbing piping. 7. Provide fused/breaker lockable 110v cab light disconnect. 8. Seal all penetrations for fire rating. 9. Existing breaker panel can remain, or be relocated. HOSITWAY Seal all penetrations in hoistway. Cover or remove wood from top of shaft and door frames 1. 2. Install door retainers on top of doors. 3. 4. Remove all unrelated wiring in holstway. All wiring in hoistway must be in conduit or of flame retardant type. PIT 1. Provide guarded light with 10 foot-candles. 3. 4. 2. Provide sump pump or drain capacity to remove 3,000 GPH (verify) Provide single GFCI or permanently wired for sump pump. All Sump pumps must be provided with a full flow check valve and gate valve. Provide convenient GFCI outlet, Provide code compliant pit ladders. Ladder with be within a 39" horizontal plane from 5.6. interlock. MISCELLANIOUS 1. Provide re-opening device - 3D detection of object in door path. 2. Install Phone failure device. 3. 4. 5. Install Emergency power illuminated signal, if equipped with stanby emergency power All lobby landings must have 10fc of lighting. Install Sprinklers in pit, machine room, or hoistway.