ASRC Federal Field LLC, (AFFS) on behalf of the government would like to propose a synopsis/solicitation for a Firm Fix Price commercial item.
AFFS intends to utilize this Request for Quotation (RFQ), under solicitation number 207084-BK, to award a FFP Low Cost/Technically Acceptable contract.
The Description of generator is list as follows:
1 EA: C60D6C Diesel Genset, 60Hz, 60kW
H268-2 Extension - Oil Drain
F253-2 Larger Battery Rack
A322-2 Packing - Skid, Poly Bag
L050-2 Literature - English
L028-2 Genset Warranty - 2 Years Base
H706-2 Engine Oil
E154-2 Coolant Heater, Extreme Cold Ambient
H487-2 Engine Oil Heater - 120 Volts AC, Single Phase
H669-2 Engine Coolant - 50% Antifreeze, 50% Water Mixture
E089-2 Extension - Coolant Drain
H527-2 Warning - Low Coolant Level
E125-2 Engine Cooling - Radiator, High Ambient Air Temperature, Ship Fitted
BB89-2 Battery Charger - 6 Amp, Regulated
A333-2 Battery Charging Alternator
D041-2 Engine Air Cleaner - Normal Duty
A422-2 Engine Starter - 12 Volt DC Motor
A366-2 Engine Governor - Electronic, Isochronous
3840 Circuit Breaker or Terminal Box (Position C) - None
3250 Circuit Breaker or Terminal Box (Position B) - None
KX30-2 Circuit Breaker, Location A, 125A - 400A, 3P, LSI, 600 Volts AC, 100%, UL
KV03-2 Load Connection - Single
H536-2 Control Display Language - English
K796-2 Stop Switch - Emergency
H012-2 Gauge - Oil Pressure
H700-2 PowerCommand 1.1 Controller
H609-2 Control Mounting - Left Facing
C318-2 Switch - Fuel Tank, Rupture Basin
C314-2 5 Gallon Lockable Spill Containment Fuel Fill Box
C312-2 Mechanical Fuel Gauge
C310-2 Low Fuel Level Switch, 40%
C127-2 Fuel Water Separator
C303-2 Fuel Tank - Regional, Dual Wall, Sub Base, 48 Hour Minimum
F179-2 Skidbase - Housing Ready
F252-2 Enclosure - Wind Load 180 MPH, ASCE7-10
P176-2 Enclosure Color - Green, Aluminum
F231-2 Aluminum Sound Attenuated Level 1 Enclosure, with Exhaust System
BB87-2 Alternator - 60Hz, Reconnect, Full Output, 105C, 40C Ambient, Increased
Motor Starting (IMS)
R098-2 Voltage - 120/208, 3 Phase, Wye, 4 Wire
B240-2 Exciter/Reg - Torque Match
L193-2 NFPA 110 Type 10 Level 1 Capable
L090-2 Listing - UL 2200
L169-2 Emission Certification, EPA, Tier 3, NSPS CI Stationary Emergency
A331-2 Duty Rating - Standby Power (ESP)
Install-US-Stat U.S. EPA, Stationary Emergency Application
1 EA: CBLC, Bypass Transfer Switch-Power Command:
150A/225A/260/300/400/600A 1 $17,845.41
A050-7 Packing-Wooden Crate
G012-7 Transfer Switch Warranty - 2 Year Comprehensive
M076-7 Standard Customer I/O
M033-7 Genset Starting Battery-12VDC
R021-7 Voltage-208 Volts AC
C109-7 PC80 Control
A044-7 Frequency-60 Hz
A078-7 Transfer Mode-Delayed Transition
A091-7 System - 3 Phase, 4-Wire (Solid or Switched Neutral)
A029-7 Poles-4
B002-7 Cabinet-Type 3R
A035-7 Application-Utility to Genset
A046-7 Listing-UL 1008/CSA Certification
Delivery charges will need to be included in quote.
All interest offerors will need to be sent via email to betty.kliewer.ctr@us.af.mil NLT 11/11/25 at 11:00AM CST. No late entries will be excepted.
Attached are forms that will need to be completed before an award will be made.