GENERATOR Stationary Emergency Generator to include all installations, labor, materials, permits, and inspections for project: Generator shall be as follows: 1. Kohler 100REOZJ 2. 100kW 3. 277/480 Volt 4. 3-phase 5. 153 Amps standby engine 6. Meets NFPA 110, UL2200 listed and EPA Certified Tier 3 standards. 7. Generator set and components prototype tested, and production tested according to the UL test program ENGINE 1. John Deere diesel fueled 2.2 Liter 4 cylinder turbocharged. 2. Permanent Magnet Generator (PMG) 3. Electronic governor 4. Dry type filters 5. Vibration isolators between engine-gen and skid 6. Oil and coolant drain extended to Genset base rail. 7. United mounted radiator with shell and fan guard. 8. 12-volt starter and alternator. 9. Starting batteries with cables and mounting tray. 10. Battery charger 10-amp. 11. 1500-Watt Block heater. 12. 120V, 1 Ph, 175 Amp Main 100% rated adjustable 3-Pole main line circuit breaker with electronic trip mounted in connection box. 13. Generator 1800 RPM brushless type excitation. 14. 60 Hz, three-phase, 277/480-volt, thermal overload protection. 15. Class H insulation.