Wet Well: Wet Well shall be 6 ft diameter precast concrete and shall meet the specifications in the Wastewater Gravity System standard under “Wet Well Requirements and Design”, which includes but is not limited to the following Structure: • Epoxy Coat wetwell walls and piping • Reinforced concrete cover constructed to accommodate the above ground station pump station components and enclosure, reinforced around openings as shown on the drawings. • Semi-circle access cover and pump frames shall be double leaf aluminum diamond pattern floor hatch certified for H 20 loading. Leaves shall open 90 degrees attached with Stainless steel hinges that lock in the open position and vinyl grip handles to release lock for closing. • Safety landing grating constructed of stainless steel with coated orange or safety yellow by “Retro-grate” or equal. Pump Station Appurtenances: Furnish and install all pump station components and appurtenances as shown and specified in Moore County’s “Wastewater Lift Stations and Force Mains” standard including but not limited to the following as: • Ventilation Equipment • Auto-dialer (remove and reinstall the existing Auto-dialer) • Flow monitoring equipment (not required for this size station) • Alarm light and horn • Standby Power