Specifications include, but are not limited to: 1. Existing Equipment provided by the owner. a. S2 Controller is Provided by the owner and is part of the current access control system. Currently licensed for 512 doors. Any expansion for these monitored doors will be provided by the contractor and included in your bid. b. Access Control reader and locking hardware at the current access-controlled entrances for each facility is not part of this proposal and is already provided with the current system. These locations do not currently have door position switches and are required to be installed under this contract. c. Existing network nodes that have open slots may be used for adding S2 Input Blades for new monitored doors. Additional nodes required for this project shall be included in your bid. 2. Manufactures a. Lenel S2 b. GRI (or equivalent) c. West Penn Wire (or equivalent) 3. Monitored Door Locations a. All exterior doors listed as monitored doors and shall have a set of door N/C contacts wired to an individual input on the access control system. This will be used to notify the staff if a door is propped open. b. Each “Entrance” shall be a separate monitored Input point on the system. If an entrance has two doors, each door will have one set of contact wired in series on one input to the system for that entrance. Maximum of two door contacts on any single input. Separate entrances and doors may not be daisy chained on one system input. Installation contractor shall install additional input boards on the system as needed. 4. Door Contacts a. Provide appropriate door contacts for every exterior door as identified. b. Access controlled doors will have one door contact associated with the controlled door at that entrance. If that location is a double door Entrance, install a separate set of contacts on a separate input to be programmed as a monitored door on the system. 5. Door Controllers a. Network Nodes with Input Control boards shall be mounted in MDF/IDF locations only unless approved by the owner for specific locations. b. Network Nodes with Control Board Cabinets are to mount at 4’to 6’ AFF for easy service. c. Provide data drop from each new Network Node to the owner’s nearest POE network switch.