1. One (1) Cummin C60N6, 60kw, Standy, Natural Gas/Propane Genset Generator with the following: A. U.S., EPA, Stationary Emergency Application B. Duty Rating - Standby Power (ESP) C. Emissions Certification - SI, EPA, Emergency, Stationary, 40CFR60 D. Listing - UL 2200 E. NFPA 110 Type 10 Level 1 Capable F. Exciter/Regulator - Permanent Magnet Generator, 3 Phase Sensor G. Voltage - 277/480, 3 Phase, Wye, 4 Wire H. Alternator - 60Hz, 12L, 480/277V, 105C, 40C Ambient, Increased Motor Starting (IMS) I. Alternator Heater, 120 Volt AC J. Aluminum Weather Protective Enclosure, with Exhaust System K. Enclosure Color - Green, Aluminum L. Battery Rack M. Skidbase - Housing Ready N. 3% Line Impedance as Standard O. Enclosure - Wind Load 180 MPH, ASCE7-10 P. PowerCommand 1.1 Controller Q. Gauge - Oil Pressure R. Warning - Low Fuel Gas Pressure S. Stop Switch - Emergency T. Relays - Auxiliary, Qty 2, 25A - 15V DC/10A - 30V DC U. Control Display Language - English V. Load Connection - Single W. Circuit Breaker, Location A, 125A, 3P, 600 Volts AC, 80%, UL X. Circuit Breaker or Terminal Box (Position B) - None Y. Circuit Breaker or Terminal Box (Position C) - None