The RUP maintenance services needed include, but may not be limited to, the following: • Standard and OEM monthly, quarterly and annual preventative maintenance for each component type. • Emergency response during standard working hours of 7:00am through 3:30pm, Monday through Friday. • After hours emergency response within two (2) hours of receiving the service call; after hours calls will be billed separately from standard service contract billing. • Restore systems commissioned settings where drift has occurred. Recommend system settings adjustments for improved performance in high load, intermittent load, and low load conditions. Provide new recommended settings in writing to the University representative. • Use vibration analysis, electric current motor analysis, and thermal analysis to detect and diagnose equipment failure modes where appropriate. • Inform the University representative of any required water chemistry changes needed to optimize system performance. • Laser align motors and pumps when required. • Provide recommended updates to drawings and other University provided information that is discovered to be incorrect.