CONSTRUCT NEW GENERATOR MOUNTING PAD a. Provide a steel-reinforced, cast-in-place concrete pad; dimensions shall be based on the footprint and weight of the fuel tank/generator combination when fully fueled. b. Proposed pad location shall be marked in the field for review/approval by ONWASA prior to construction. c. The proposed location shall allow a four-foot (4’) minimum clearance between the existing fence and the generator installation site. d. The contractor is responsible for leveling the ground at the concrete pad site if required. INSTALL NEW FUEL SUPPLY TANK a. The Contractor shall furnish and install a new 1000-gallon base-mounted double wall fuel tank on the concrete generator mounting pad. b. The Contractor shall furnish and install a new fuel pick-up line, fuel return line, and all other components necessary from the generator to the fuel tank to provide a fully functional system. c. Exposed fuel pick-up line and return shall be securely mounted to the concrete slab with a non-corrosive mounting system suitable for this application and shall be painted safety yellow. d. The tank dimensions SHALL NOT allow the installed height of the generator to exceed six feet (6’) from the finished grade to the top of the generator. e. The tank shall be shop-fabricated and capable of mounting to the concrete slab...