Removal of existing propane supplied generator and replace with a diesel supplied generator. Full installation utilizing the existing infrastructure including automatic transfer switch, electrical and conduit. Include the delivery, installation, factory authorized commissioning, battery, and with removal/recycling of the old generator. Industrial automatic diesel generator, 130kw, 3-phase 277/480 volts, 175-amp breaker, level 2 sound deadened 72 decibel enclosure, FPT 6.7l inline 6-cylinder turbo diesel engine, 1800rpm, battery charger, block heater and is mounted on top of a 350-gallon 36-hour subbase diesel fuel tank. It should go 64 hours at half load, 120 hours at a quarter load. This unit should be UL2200 and NFPA 110 rated, and has a limited 2-year, 1000-hour warranty.