A. A. A. B. A. B. C. A. 1. 2. 3. 4. 5. 6. 7. 8. 9. 10 11. Warranty The breakers shall have a minimum warranty of at least 12 months from the date of delivery. Optional Expanded Warranty - The vendor shall provide an optional quote to extend the warranty for an additional 5 years beyond the base warranty. Project Deliverables Circuit breakers shall be interchangeable with existing breaker wiring diagram 0209B8264P002, Serial No. 0129A8772-001-01 (3000 A). Bidders must supply breaker wiring diagrams with bid. The equipment must have been manufactured within the previous 18 months as of the date of the delivery. Breaker must have new vacuum bottles. Please see the Instruction to Bidders Section for Information on Liquidated Damages. Schedule Specify delivery date and lead time on bid response. Supply one (1) new GE breaker for installation in existing 4 kV switchgear vacant breaker cubicles. Specifications Type: VB1H-4.16-350-0 3000 A, 4.76 kV, 60 Hz Rated Voltage Range Factor = 1.19 Rated Short Circuit = 41 KA Impulse Withstand = 60KV Close and Latch = 78 KA Interrupting time = 5 cycles Motor Voltage = 125 VDC Close Voltage = 125 VDC Amps = 6.0 Voltage Range = 100-140 VDC Trip Voltage = 125 VDC Amps = 5.9 Voltage Range = 70-140 VDC Connection Diagram= 0209B8264P002 Vacuum Interrupter Type= 43B1