Specifications include, but are not limited to: Replace the existing 175 kW generator with one (1) 150 kW 120/208V, 3-phase,4 wire diesel Kohler #150REOZJF generator (or equivalent), incl. one (1) 400 amp Line Breaker, NFPA 110 Level 1 digital controller, pad mount generator with exterior sound enclosure. Rework existing generator pad and U. G. conduits /conductors for new generator as required.•Provide minimum of one (1) year manufacturer’s Warranty.•Replace existing automatic transfer switch with one (1) 400-amp NEMA 1 Kohler#KSS-ACVA-0400S (or equal) ATS unit. (The existing Fire Station ATS is to remain.)•Rework the existing interior conduits / conductors from generator to both existing ATS units, existing wire trough, panels and re-label for correct service entrance requirements.