Specifications include, but are not limited to: Multiconductor control cable with shield, 600V for use in 345kV substation. The cable shall be twelve (12) 10 AWG 7 strand, bare copper conductor with flame-retardant XLPE or EPR insulation and polyvinyl chloride (PVC) or Chlorinated Polyethylene (CPE) jacket. Bare 5 mil corrugated copper tape longitudinally applied shield. Suitable for utility company substation and power plant control circuits and use in open air, ducts, trays, conduit or direct burial, indoors or outdoors. Rated at 90C wet or dry, sunlight, heat, flame, moisture and chemical resistant, would prefer low coefficient of friction for pulling. Conductor colors to follow code Method #1 Table E1. Cable shall be supplied on 1000FT non-returnable reels.