Specifications include, but are not limited to: Fire Alarm Control Panel Requirements: ▪ Hardware and Software • Panel shall be capable of supporting at least 2500 devices. • Panel shall store event history of last 1000 events • Panel shall allow for at least two user access levels o One level of password shall be a master password, the County will assign this password o User password ▪ Minimum of 5 user passwords ▪ This access level would allow devices to be disabled • The fire alarm control shall have a time of day display that shall not be lost in the event of a primary and secondary power failure. • The fire alarm control panel shall have a non-volatile memory for the programming. • Panel shall support a communication network of copper, multi-mode or single-mode fiber optic, or all three simultaneously