Specifications include, but are not limited to: ➢ The Contractor shall purchase and install a fire pump controller rated for a 75-horsepower pump motor. The controller power is supplied with 480-volt, 200-amp feeders. ➢ The Contractor shall be responsible for any electrical conduit that may need to be reconfigured to accommodate the controller in place of the existing one. ➢ The Contractor shall be responsible to perform a system test to verify proper operation of fire pump controller. ➢ The Contractor shall replace the fire pump controller and have system back in service before leaving the site for the day. Any overtime associated with this shall be included in this bid. ➢ The Contractor shall provide a fire pump controller that includes the fire alarm supervisory alarm points, fire pump running, fire pump controller loss of power, fire pump power emergency power.