Specifications include, but are not limited to: a. Add motor operators to service disconnect circuit breaker at the Hatchery Building and Well Houses 1 thru 7. b. Add a remote pushbutton station for service disconnect circuit breaker at the Hatchery Building and Well Houses 1 thru 7. c. Modify the service entrance section of MCCs 1 thru 8 at the Hatchery Building and Well Houses 1 thru 7 to fully isolate that compartment from all other components in the motor control center, to provide a sufficient seal to keep ionized/conductive gasses produced during an electrical fault in the motor control center isolated from the service entrance compartment during normal clearing time for the service entrance circuit breaker. d . Add modifications to service disconnect circuit breaker at the Hatchery Building and Well Houses 1 thru 7 replacing lugs to accommodate conductors terminated to the supply and load side of the service disconnect circuit breaker.