Specifications include, but are not limited to: o The finished well shall be a 4-inch nominal diameter well to a depth of approximately 100 feet, depending upon the location and depth of the water bearing strata. o The completed well shall consist of these main items: A hole drilled to a depth of approximately 100 feet below the existing ground level. A 4-inch diameter steel casing with an overall length of at least 80 feet. A 4-inch nominal size screen with a minimum length of 4 feet. o The desired capacity of the new well is at least 10 gal/minute for continuous operation. o An 8-foot bury Maass weld-on sanitary pitless underground discharge unit, or approved equivalent o A Grundfos submersible pump model 10 SQ 05-160. o 1-1/4” Dia. Schedule 80 PVC drop pipe o 10-3 w/ground Type U.G. power supply wire o 1 1/4” Pressure Class 160 High Density Polyethylene pipe (5’ bury depth below exist. ground) o Installation of all necessary piping, plumbing supplies, and electrical power cable to operate the water supply system as shown on the plans and specifications.