EMOVE ALL ELECTRICAL EQUIPMENT, WIRE, CONDUIT, ETC ASSOCIATED WITH DEMOLISHED EQUIPMENT. 5. REMOVE ALL ABANDONDED ELECTRICAL CONDUIT AND WIRE BACK TO SOURCE. 6. PROVIDE SHOP DRAWINGS FOR THE FOLLOWING: A. CONDUIT. B. CONDUCTORS. C. WIRING DEVICES INCLUDING COVERPLATES. D. DISCONNECT SWITCHES, ENCLOSED CIRCUIT BREAKERS AND FUSED SWITCHES. E. PANELBOARDS. AND SWITCHBOARDS F. SURGE PROTECTION DEVICES 7. PATCH, REPAIR, AND PAINT ANY OPENINGS THROUGH ROOF, CEILINGS, WALLS, OR FLOORS TO MATCH EXISTING CONDITION. 8. THE OWNER SHALL HAVE FIRST RIGHT OF REFUSAL OF ALL DEMOLISHED EQUIPMENT. 9. PROVIDE LAMACOID LABELS FOR: A. PANELBOARDS AND SWITCHBOARDS. B. DISCONNECT SWITCHES. 10. MINIMUM CONDUIT SIZE SHALL BE 1/2" TRADE SIZE. 11. USE THE CONDUIT TYPE SUITABLE FOR THE ENVIRONMENT IN WHICH IS IS LOCATED: A. INDOORS: EMT WITH SET SCREW FITTINGS. MC CABLE IS ACCEPTABLE FOR BRANCH CIRCUITS WHERE CONCEALED. B. CONDUIT EXITING FROM UNDERGROUND SHALL TRANSITION TO EMT/RGS PRIOR TO BEING EXPOSED. 12. PROVIDE CONDUIT SLEEVES FOR LOW VOLTAGE DATA CABLING. 13. ALL CABLING SHALL BE IN CONDUIT UNLESS ABOVE AN ACCESSIBLE CEILING WHERE "J" HOOKS ARE ACCEPTABLE. 14. USE CONDUIT SWEEPS FOR ALL DATA CABLING CONDUITS. 15. DATA BOXES SHALL BE DOUBLE GANG, 3 1/2" DEEP WITH SINGLE GANG MUD RING WITH 1" CONDUIT TO ABOVE ACCESSIBLE CEILING...