Specifications include, but are not limited to: PERFORMANCE OF SERVICES Provide and install: Kohler 150 REOZJF rated 154KW, 277/480 volt, 3 phase, 60 Hz with the following equipment: UL2200 Cooling system to be unit mounted radiator Permanent Magnet Alternator Engine Jacket Water Heater 6 Amp Battery Charger, Float Type Flexible Fuel Lines Stainless Steel Flexible Exhaust Connector Critical Grade Exhaust Silencer 12 Volt Lead Acid Starting Batteries with Rack & Cables Open Unit Sub-base Tank 298 gallons (24 hours) UL 142 Double Wall with Low Fuel & Rupture Alarms APM402 Digital Controller, NFPA 110 Level 1 with Run Relay Electronic Isochronous Governor Local Emergency Stop Button Remote Emergency Stop Button Unit Mounted Maine Line Circuit: 200 Amps Automatic Transfer Switch: 200 Amps, 3 pole, 480 V, NEMA 1 (KSS_AMTA_0200S) Initial Charges of Antifreeze and Lubrication Oil Five (5) Year Manufacturer Warranty INSTALLATION WORK TO INCLUDE: Drain, disconnect and remove and properly dispose of existing generator fuel tank Disconnect, remove and properly dispose of existing generator Disconnect, remove and properly dispose of existing exhaust components and patch building wall Rigging for removal of old and installation of all new equipment Supply and install new exhaust thimble to exterior of building Supply and install new engine exhaust system to building exterior Supply and install new radiator damper and louver system to building exterior Supply and install new intake air louver and electric damper Supply, install and connect wiring between generator and transfer switch Run fuel tank fill and vent to exterior of building Start generator and perform all function tests Check voltage and frequency and adjust if necessary Perform a One-Hour loan bank test Simulate power outage and connect generator to building Instruct owners on proper operation of generator and system File all owner warranty registration forms