Specifications include, but are not limited to: • 100% outside air hot water coil heating/chilled water coil dehumidification air handling units with energy recovery wheels providing tempered ventilation to the classroom areas • Variable air volume boxes with demand ventilation control and temperature sensor to modulate airflow based on occupancy and space heating/cooling demand for all occupied areas • Overhead fiberglass insulated supply air ductwork distribution systems connecting to ceiling mounted diffusers and fully ducted return air ductwork systems • Chilled/hot water radiant cooling/heating along exterior walls • 100% outside air variable air volume hot water coil heating/chilled water coil cooling air handling units with energy recovery wheels providing displacement ventilation to the classroom areas • Multiple four-pipe two coil heating and cooling induction units serving the administration and library areas • Variable air volume boxes with demand ventilation control and temperature sensor to modulate airflow based on occupancy and space heating/cooling demand for all occupied areas • Primary air ducted directly to induction units ; • Make-up air handling unit and variable air volume exhaust air fan system serving the kitchen • Limited use of hot water radiation and unit heaters • Water-to-water titanium heat exchangers • Four-pipe heating/cooling piping system serving all air handling units, chilled/hot water radiant panels, and induction units • Two-pipe hot water distribution system serving radiant heating panels and unit heaters • Direct digital controls throughout (Proprietary system – Johnson Controls).