Specifications include, but are not limited to: The annual routine maintenance of the diesel generators shall include but not limited to the following: 1. Inspect lube oil levels. 2. Inspect all Radiator & coolant systems. (Level, condition, temperature rating, pressure test shall all be included with each generators final report). Replace all coolant as needed based on rating test. To be approved in advanced by the D.P.W. Director prior to replacing all coolant. Replace and supply any radiator caps if needed after pressure testing are required under this contract at no additional cost. 3. Replace all radiator and coolant system filters. All filters, gaskets, O-rings, seals are to be provided under this contract at no additional cost. 4. Start up engine and generator system with prior approval from D.P.W. personnel. 5. Inspect and test all instrument control panels, gauges and displays for proper operation. 6. Secure system. 7. Change all lube oil, and all lube oil filters and all fuel filters. Clean any and all strainers as needed. All oil and oil filters, fuel filters, gaskets, O-rings or seals needed are to be provided under this contract at no additional cost. Install tune up parts if required are to be provided under this contract at no additional cost.