C. Baseline IT Baseline IT will be installed at all locations except for Pioneer Valley 1. Procure and Install Front door and back swing door, Wall mounted 19inch Cabinet 36" (19RU) x 24" Deep x 23" Wide having Key Fob locking system with cloud-based access control. 2. Procure and Install 24 or 48 port patch panel depending on the count of horizontal CAT6 cabling with same amount. 3. Procure and Install UPS. Solution can be provided with additional metered PDU equipment if needed. 4. Procure and Install CAT6 horizontal cabling to patch panel assigned per location. See network jack counts per location. 5. Procure and Install 4 port console server to access serial ports for inbound remote network access. 6. Dedicated electrical outlet next to the IT Cabinet should be terminated at NEMA L5-20R D. Hardware requirements 1. Belden XHW-3624-GD front door and back swing door Wall mounted 19-inch Cabinet 36" (19RU) x 24" Deep x 23" Wide with centralized cloud managed Access Control system (see Attachment B). 2. Certified CAT6 patch panels to be used only. 3. Cable Spec - Plenum Rated Certified CAT6 ethernet. 4. UPS - Lithium battery-based, double conversion/online UPS 120V NEMA L5-20P input with 8x NEMA 5-15R outlets, preferred switchable via network interface, includes network interface card for HTTP, SSH, SNMPv2\v3, access and monitoring. Include environmental monitoring with minimum temperature and humidity. 5. Tripp lite 4-port Console server B09-004-1E or equal to can be proposed.