Specifications include, but are not limited to: The selected vendor shall utilize existing conduct runs from the NSR911 Center to the communications pull box adjacent to the new communications shelter. The selected vendor shall provide cabling that adheres to RF (radio frequency) shielding and water intrusion standards. The selected vendor shall: Run 2” conduit from existing UPS circuit to spare 6” conduit in raised floor in equipment room within the NSR911. Reduce 6” to 2” to complete run. Install one electric pull box outside next to an existing communication pull box and redirect 6” spare conduit in and out to the shelter. At the shelter site, install one electric pull box inside the fencing and redirect spare conduit and shelter power conduit into that pull box. Install two 6U fiber splice junction boxes: One inside the communication room at the NSR911 main building One inside the shelter. Run 72-strand ST-ST fiber from communication room to shelter. Loom and seed where earth has been disturbed. Re-stone fenced-in shelter area