Specifications include, but are not limited to: The basis for this RFP document is for the sports lighting manufacturer to provide a turn-key sports lighting installation which includes all fixtures, lamps, light racks, mounting brackets/hardware, steel painting, the installation of electrical wiring and equipment, crane/erection and DMX lighting controls for a complete system that meets the criteria herein. Lumen Package – Maximum of 120,000 delivered lumens per fixture. Glare rating ≤ 40 GR at all calculation points on the field and all fixed camera positions. Maintenance Factor shall be 0.88. The use of multi-zoned aiming strategies is required. The design must fully comply with local authority light spill requirements. Final luminaire count dependent upon individual manufacturer meeting the performance lighting design criteria. All Drivers shall be electronic with less than 2% flicker. All fixtures in the endzone (Racks A2, B2, C2, D2) shall have additional glare mitigations shields.