Specifications include, but are not limited to: • Roof-top installation w/ new curb (curb shall be supplied with the air handler) • Natural Gas Heating – Stainless Steel Construction • Hot Gas Reheat • Packaged Cooling • Energy Recovery • 2” – MERV 8 Pre-filter/ 4” – MERV 13 Filter • Full onboard controls. • Voltage - 460/60/3 • The Unit shall be ASHRAE 90.1 – 2016 Compliant.; • Nominal Air Flow – 1,000 CFM, 100% Outdoor Air • Hot Gas Reheat Coil Modulating Capacity Control 54°F EAT, 70°F LAT • Gas Heating Stainless Steel Construction 70°F EAT, 80°F LAT 7” – 14” Gas Pressure 10:1 Turndown • Cooling 81°F EAT DB, 69°F EAT WB 54°F LAT DB, 54° LAT WB 95°F Ambient Air Temperature Stainless Steel Drain Pan • Energy Recovery Summer 95°F DB, 78°F WB Outside Air 75°F DB, 62°F WB Return Air 81°F DB, 69°F WB Supply Air Winter 10°F DB, 9°F WB Outside Air 70°F DB, 50°F WB Return Air 51°F DB, 39°F WB Supply Air