Specifications include, but are not limited to: Install 2 3/8 inch diameter galvanized steel posts of 0.095 inch wall thickness and 6 (six) foot length spaced no further than 10 (ten) feet apart. Drive the posts a minimum of 36 (thirty- six) inches into the ground. Fasten 9 gauge or heavier galvanized chain link fence (2 3/8 inch maximum opening) 42 inches in height securely to the fence posts with wire ties or hug rings. Fasten woven silt film geotextile as specified in section H-1 materials securely to the upslope side of chain link fence with ties spaced every 24 (twenty -four) inches at the top and mid-section. Embed geotextile fence and chain link fence a minimum of 8 (eight) inches into the ground. Where ends of the geotextile come together, the ends shall be overlapped folded and stapled to prevent sediment by pass. Extend both ends of the super silt fence a minimum of 5 (five) horizontal feet upslope. At 45 (forty-five) degree to the main fence alighnment.to prevent runoff from going round the ends of the super silt fence. Provide the manufacturer certification to the inspection / enforcement authority showing that the geotextile used meets the requirements in section h-1 materials.