Specifications include, but are not limited to: The replacement of a communications shelter. located at the Town of Snow Hill water tank located on North Washington Street in Snow Hill, MD. The County desires to replace the existing fiberglass shelter with a new concrete shelter as a turn-key project with minimal site disruption. Contractor shall furnish one pre-fabricated communications shelter consisting of an equipment room and generator room. The shelter shall be nominally sized 12x28x10 foot (height is interior dimension). Shelter shall incorporate non-porous wall and roof sections, to preclude capillary action, and shall be so designed, and constructed to provide a minimum useful life period of 20 years, without need for major maintenance actions. The wall outer finish shall be natural stone aggregate with an aesthetically pleasing earth tone. Finish selections shall be submitted for review with final selection by the owner. The minimum floor loading design shall be 300 pounds per square foot. The minimum roof loading design shall be 100lbs per square foot. The minimum wall loading design shall be 34lbs per square foot.