Specifications include, but are not limited to: Bring power in conduit from the main building to a shed that houses an automated brine production system. This consists of a control unit with pumps inside a shed and a hopper outside of the shed. 20A 240V single-phase circuit to the hopper. 60A 208-220V 3-phase circuit is preferred for the control unit. 60A 240V single phase circuit is suitable as well. Wire two (2) dedicated outlets for shed space heaters.; Brine Making System is intended for use as a generator of quality salt brine that is used as a prewetting, anti-icing, and/or a de-icing agent on pavement or roadways. The system is the Brine Xtreme Infinity by Henderson. Contractor will also supply power to internal/external components including but not limited to automated brine control units, brine maker hopper, various electrical wall, and ceiling receptacles and automated brine supporting apparatuses. ; Automated Brine Production System Scope of Work (Electrical): Bring power in conduit from the main building to a shed that houses an automated brine production system. This consists of a control unit with pumps inside a shed and a hopper outside of the shed. 20A 240V single-phase circuit to the hopper. 60A 208-220V 3-phase circuit is preferred for the control unit. 60A 240V single phase circuit is suitable as well. Approximately 50-75’ run between building electrical supply and Automated Brine Making system. Wire two (2) dedicated outlets for shed space heaters.