Specifications include, but are not limited to: 1. Buildings shall be wood framed with steel roofing and siding. There shall be no obstructions with in the floor area.2. The roof shall have a 5:12 pitch or greater.3. Concrete foundation to include a placed 8”x 8” concrete curb wall (no Blocks)around the whole perimeter.4. Roof to include vapor barrier and a continuous ridge vent. The eaves/soffits shall have vents as needed and determined by the Engineer of the pre-engineered building.5. The sill plate shall be constructed with pressure treated lumber.6. The garage doors shall be a commercial grade with struts. The color shall bewhite with no windows. Minimum insulation value of R15, Insulation type will be foamed in place CFC free Polyurethane core, minimum of 26 gauge exteriorand interior steel skin sections, heavy duty adjustable top roller brackets Section joints will be tongue and groove, Commercial grade door and attaching hardware.7. The siding shall be constructed with a maximum 8’ high steel sheathing from the ground to the first joint so that if damage occurs only the 8-foot piece will need replacing.8. The steel siding and roofing shall be attached by stainless steel screws.9. The steel roofing and siding shall be a minimum 26 gauge. 10. The concrete slab will be sloped (¼” per foot) 4-6 feet from the outside edge at all garage door openings so that water runs out of the building.