The ratings shall be as set forth below: a) Continuous Current (Amps) 2,000 b) Maximum Voltage Rating (kV) 245 c) Phases 3 d) Frequency (Hertz) 60 e) Voltage Range Factor K 1.0 f) Type of Interrupting Medium SF6 Gas g) Maximum Symmetrical Short 40 Circuit Current Capability (kA) h) Three (3) Second Short Time 40 Current Carrying Capability (kA, RMS) i) Close and Latch Capability (kA, Peak) 104 j) Withstand Test Voltage (kV) Low Frequency, 1-Minute Dry 425 Full Wave Impulse 900 k) Trip Control Voltage (DC Volts) 125 l) Close Control Voltage (DC Volts) 125 m) Maximum Interrupting Time (Cycles) 3.0 n) Closing Time (Cycles) 6.0 o) Reclosing Time (Cycles) 20 p) Permissible Tripping Delay Y (Seconds) 2.0 q) Mechanical Endurance Operations 10,000