Specifications include, but are not limited to: Generator full service with load bank testing on installed generators An annual load bank test is required of 50% load for 30 minutes and 75% load for 60 minutes (2- generators of 800kw, model # DQCC-121158, serial # I120390519 and 1- generator of 350kw, model # DFCC-5604065, serial # F-30511937) **Inspection on storage batteries, including electrolyte levels or battery voltage, used in conjunction with systems **Inspection and testing on automatic transfer switches: (3) ONAN ATS and (1) EMERSON ASCO (Switch test: normal to emergency operating), electronically operated switches. (Serial numbers include: C030479178, 639264, C030479179, C0304791) **Diesel tank testing on (3) tanks; Check diesel in all tanks and provide reports