These specifications are prepared for a contract to remove the existing equipment and to furnish and install a three (3) ton system with a gas furnace for Galatas Gym (which serves upstairs offices) located at 41 Nassau Avenue for the City of Kenner, Department of General Services. The contract will entail providing all necessary labor, materials, equipment, tools and incidentals and made a part hereof including any and all necessary duct work, transition work, electrical work and work associated to properly remove and install specified equipment. All equipment installed is to be of new and current manufacture and is to be in proper working order as designed by manufacturer upon completion of job. All electrical shall be modified/upgraded to accommodate the voltage and amperage of new equipment including any and all new electric disconnect boxes, wire, conduit and fuses. All electrical shall be performed solely by local or state licensed electricians and shall meet all local state and Federal codes. TS-1 REMOVAL OF EXISTING EQUIPMENT: Contractor is to properly remove and dispose of indoor evaporator coil, gas furnace, refrigerant, copper and outdoor condensing unit. TS-2 EQUIPMENT: Contractor shall furnish and install one (1) 15 SEER American Standard 3-Ton System (or equal) with a gas furnace. American Standard (or equal) equipment shall contain the following factory options: • Furnace, Model S8X1B060M4PSC, with insulated cabinet • Evaporator, Model 5TXCB004AS, with TXV • Outdoor Condensing Unit, Model 5A7A5036A, with low ambient kit Fabricate and install necessary sheet metal transition with canvas connector for supply duct. Route new refrigerant line set from indoor evaporator to outdoor condensing unit. All associated copper shall be Type L hard drawn. Insulate with a ¾” rubbertex and paint with UV resistant paint. Provide a new Honeywell Programmable Thermostat to be mounted in the office. Furnish new high limit control in return air duct and install SS-2 safety switch on evaporator pan. Provide 3” lightweight outdoor slab to set underneath new condensing unit. Furnish and install one (1) new Square D side arm commercial disconnect box, fuses and electrical whip. All control wire shall be routed in electrical conduit to thermostat and outdoor condensing unit. Route 1” PVC condensate drain and insulate. Replace all double wall vent pipe and re-pipe gas line. No flex will be allowed. Perform system startup and programming. Provide one (1) case of 2” filters.