1. Inspect systems annually to include all sprinklers, hangers, pipe and fittings(escutcheon rings included) 2. Verify that system appears to be free of physical damage 3. Conduct a main drain test and verify water supply availability 4. Visually inspect control valves to ensure that they are a. In the normal position b. Accessible c. Properly sealed d. Locked or supervised e. Free from leaks f. Appropriately labeled as to function 5. Test and maintain control valves 6. Test valve tamper switches, where installed, for proper signals 7. Test water flow devices, by water discharge 8. Visually inspect gauges to ensure proper pressures are being maintained 9. Test antifreeze solution, if applicable 10. Inspect the fire department connections to verify that a. They are visible and accessible b. Couplings and swivels are not damaged c. Gaskets are in place and in good condition d. Plugs or caps are in place and not damaged e. Ensure check valves are not leaking 11. Ensure a minimum supply of sprinkler heads are provided at each riser according to NFPA 12. Provide service tag on each riser 13. Provide NSU Facility Services with a written report of inspections