The Contractor shall provide all of the materials and perform all the work described in the Specifications and/or shown on the Drawings. Sprinkler Heads will be replaced per KBC "Kentucky Building Code", NFPA 13 "Standard for Installation of Sprinkler Systems" and the IBC "International Building Code". All Sprinkler heads in the Guest Rooms will be replaced with fully concealed sprinkler heads and flat plates, white in color. Sprinkler heads (in outdoor canopy areas) shall be wax coated, rough brass finish in all exterior and wet locations. Sprinkler heads shall be white color (in light ceiling areas) in ACT or gypsum ceilings. Sprinkler heads will be rough brass finish in the attic and other dark color areas. The Dry Riser including all check valves, air compressor, alarm valve, gate valves, pressure switches, tamper switches, all riser trim, all riser gauges, including the double check detector assembly, and post indicator valve will be replaced. A fire department connection will be added near the Front Entrance. Clarify that the work is to be conducted on the site of a State Resort Park and will remain partially occupied during the entire contract period. Work to be performed within the facility is to be coordinated with the Owner's Representative (Superintendent or Maintenance Supervisor) on a daily basis.