Specifications include, but are not limited to: Resistograph drilling procedure done with two ground level drills using a 1/8” bit at a 45-degree angle. The second drill point will be 90 degrees from the first drill point. 2. The inspection shall consist of the following information a. Pole number-specifics will be decided after the bid is awarded. b. Pole manufacture year and type c. Pole height d. Pole class 3. Insect damage/infestation 4. Rotting or decay of structure and any splits or cracks 5. Note any other utility attachments 6. Note all Right-of-Way items such as trees or brush in pole vicinity 7. Sound the pole at least 10 times, at ground level, in at least 4 different locations around the pole, as high as the inspector can reach standing on a ground level with a 22oz hammer for any above ground rot.