Specifications include, but are not limited to: All components and accessories shall be new, serviced and ready for operation upon delivery. •10 HP (minimum), 6000 psi, 13 SCFM (minimum), 120/208 3 phase SCBA Air Compressor shall have low & high pressure settings and include Carbon Monoxide detection with audible and visual warnings that detect down to 1 PPM. Filtration system must meet or exceed the CGA Grade E breathing air standard or any other standard for compressed air for human consumption. There shall be an audible and visual warning for compressor shutdown due to filtration issue and automatic shutdown to not allow the SCBA bottles to be filled with contaminated air. (All items shall be NFPA compliant). •Dual SCBA bottle enclosed fill station shall be designed for filling two (2) SCBA bottles simultaneously or separately. Unit shall include all proper gauges, regulator valves and fill control valves. (Shall be NFPA compliant). The enclosure shall be designed to contain the impact of suddenly expanded high pressure air and all displaced fragments in the event of a cylinder or fill component rupture. NO EXCEPTIONS. •A 100’ external fill hose with proper connections and reel are to be provided. •The breathing air storage system shall be integral to the appliance and include all cylinders, plumbing and hardware. •Three (3) 6000 psi DOT cascade bottles. All cascade bottles shall be securely mounted to the wall