Specifications include, but are not limited to: STACKED/VERTICAL UNIT WITH 208V/60HZ/3PHASE MOTOR *UNIT WILL HAVE AN UP BLAST COUNTER CLOCKWISE FAN CAPABLE OF PRODUCING +/- 5,000 CUBIC FEET PER MINUTE *AIR HANDLER WILL BE EQUIPPED WITH A RE-HEAT COIL, MINIMUM OF 185,000 BTU-HR. WITH COPPER TUBES AND ALUMINUM FINNED HEADER *THE CHILLED WATER COIL WILL HAVE COPPER TUBES AND ALUMINUM FINNED HEADER WITH STAINLESS STEEL DRAIN PAN PRODUCING A MINIMUM OF 185,000 BTU/HR *UNIT MUST BE CAPABLE OF BEING DISASSEMBLED TO PASS THROUGH A STANDARD 34" DOOR OPENING *ACTUAL UNIT SIZE WILL NOT EXCEED 60" W X 74"L X 74"H *PLUMBING AND DOOR ACCESS WILL BE ON THE UNIT'S LEFT SIDE *OUTSIDE AIR DAMPERS MUST BE LOCATED AT TOP OF RETURN BOX AND REAR OF RETURN BOX.