Specifications include, but are not limited to: S&C Electric Company (no exceptions), PMH-11 Switchgear, Jack Trice Sports Performance Center June 1, 2020 2 1 S&C Electric Company (no exceptions), SF6 Vista 413 Switchgear Jack Trice Sports Performance Center June 1, 2020 3 1 1500kVA, 13.8kV: 480/277V, Oil Filled Pad-Mounted Transformer, Jack Trice Sports Performance Center June 1, 2020 4 1 750kVA, 13.8kV: 480/277V, Oil Filled Pad-Mounted Transformer, Jack Trice Sports Performance Center June 1, 2020 5 1 300kVA, 4160V: 208/120V, Oil Filled Pad-Mounted Transformer, Parking Lots 2020 Pavement Preservation ; Item #1. Provide 1 each S&C Electric Company (no exceptions) -- Model number to be similar to part #55362R4-E3-K10, per the following specifications. 1. Model type: PMH-11. 2. Nominal rating of 14.4 KV. 3. BIL of 95KV. 4. Switch and bus continuous rating of 600 amp. 5. Mini-Rupter switches: 600 amp, 3 phase in compartment numbers 1, 2, and 4. 6. Uni-Rupter switches: Loadbreak fusing capability in compartment number 3 utilizing the SML-4Z, 200 amp fuse holders. 7. Short circuit current rating of 12,500A, RMS, symmetrical (310MVA at rated voltage). 8. Color to be ANSI green. ; Item #2. Provide 1 each S&C Electric Company (no exceptions)- 1. Rated 15.5 kV, 95 kV BIL. 2. Three phase SF6 load-interrupter switches, three position-(closed, open and grounded). Manual switch operation shall open or close all three phases simultaneously. Manual operation required to place the switch in the grounded position. 3. 600 AMP continuous and load break. 4. Momentary and close into fault rating as specified above. 5. Potential Indication with test feature consisting of LCD display to indicate presence of voltage on each phase with solar panel to supply power for testing of complete voltage-indication circuit. 6. 600 AMP Apparatus Bushings with copper studs. 7. Switch ratings per ANSI C37.71-1984 and C37.72-1987.