Specifications include, but are not limited to: At a minimum, all units shall be tested for the following: 4.1. No-Load losses at rated current *No load losses will be reported at 95 °C or 20 °C for 75 °C AWR units, and 85 °C or 20 °C for 65 °C or 65/75 °C AWR units. 4.2. Total losses at rated current *Total losses and impedance values will be reported at 95 °C for 75 °C AWR units, and 85 °C for 65 °C AWR units. 4.3. Percent Impedance at rated current 4.4. Excitation current (100% voltage) test 4.5. Winding resistance measurement tests ; 15 - 50 kVA Transformers: Conductor range to be 350 KCM str - 12 sol, to fit 5/8”-11 transformer stud. Utilco catalog #PTF6-350-CJNUSLP or equal is acceptable. 100 kVA and 167 kVA Transformers: Conductor range to be 500 KCM str - 12 sol, to fit 1”-14 transformer stud. Utilco catalog #PTF6-500CJUSLP or equal is acceptable. ; At a minimum, all units shall be tested for the following: 4.1. No-Load losses at rated current *No load losses will be reported at 95 °C or 20 °C for 75 °C AWR units, and 85 °C or 20 °C for 65 °C or 65/75 °C AWR units. 4.2. Total losses at rated current *Total losses and impedance values will be reported at 95 °C for 75 °C AWR units, and 85 °C for 65 °C AWR units.