QUESTIONS & ANSWERS:
To date, this is to post questions recevied, and Government Responses:
QUESTION #1: Do you have the Okonite Part Number?
ANSWER: To clarify, this requirement is NOT a "Brand Name Only." Currently, the Base' current infrastructure uses Okonite. The requested Cable, 15kv, #2 AWG Cu, MV90, must simply meet the specifications / salient characteristics as described in the requirement document. The wire must be compatible with the existing Okonite. If Okonite were to be proposed, the customer would request part number is 115-23-6211.
QUESTION #2: Could you kindly confirm the following detail regarding the first item, AWG Stranded Bare Copper:
Should the bare copper be soft-drawn, medium-drawn, or hard-drawn?
ANSWER: The #2 AWG Bare Copper it is hard drawn.
----------------------------------------------------
Electrical Wires
Mountain Home AFB, ID 83648
This is a combined synopsis/solicitation for the Electrical Wires IAW the attached solicitation documents.
Please see the attached solicitation/RFQ and applicable attachments.
All offers are due no later than 09 July 2025 at 12:00pm MST. (Local)