Specifications include, but are not limited to: Generator at prime: 60 kW or above. • Generator shall be equipped with a diesel engine with a speed of 1800 RPM • The generator shall have convenient access panels for easy repair of diesel engine and alternator. • Diesel engine shall have a fuel tank sized for a minimum of twenty-four (24) hours run time at full load. • Fuel filler shall be located within the containment basin to reduce fuel spillage. • Engine shall have a low fuel shutdown to ensure engine will not lose its prime if the engine runs out of fuel. • Fuel tank shall be mounted within the skid base, with double wall protection. • Generator shall provide gauges for engine and generator parameters. • Generator shall be equipped with one (1) 50 ft. cable and one (1) 100 ft. cable for tying into a transfer switch with factory connectors at one end.