Specifications include, but are not limited to: Burn Building1. NFPA 1402 compliant 2. Single-story structure 3. Approximate Dimensions: 16 ft wide x 40 ft long x at least 8.5 ft tall i. (must fit on existing concrete pad: 28 ft wide x 40 ft long, building width can vary some, building length can’t be greater than 40 ft) 4. Structure must be made primarily from weathering steel or similar strength steel, exterior to be coated with high grade industrial paint 5. Structure must sit on top of existing concrete pad (dimensions above) 6. Structure must be movable/transferable to a new site if needed (disassembled and reassembled within 3 working days, potential new site would be located within Forsyth County) 7. Fully insulated burn room rated for Class “A” and LPG fuel required 8. Movable/reconfigurable interior walls required 9. Temperature monitoring system required 10. Pricing must include delivery, on-site assembly, and burn building training conducted by certified instructors 11. Acceptable options to quote if available, please quote each separately: shoring prop, wall breach prop, exterior stairs for active roof area with OSHA compliant guardrail system, pitched roof prop, forced entry door, Denver window, and bar cutting prop Flashover Simulator 1. NFPA 1402 compliant 2. Two compartment design - upper compartment is the burn chamber and lower compartment is the observation chamber, burn chamber (upper compartment) should be approximately 3 ft higher than the observation chamber (lower compartment).