Specifications include, but are not limited to: 1) General a) The Contractor shall supply and install ten (10) generator automatic transfer switches (ATS). The purpose for the ATS is to provide automatic generator start during power outages at city lift stations to prevent sewer spills. The ATS must transfer electric power back to utility automatically when utility power is restored and shut the generator down. ATS units will be installed at existing lift stations with diesel generators currently utilizing manual transfer switches. Existing receptacles, emergency breakers, or external switches will remain in the unlikely event a portable generator is needed at these locations. b) Contractor shall provide concrete pads or racks where required. c) Installations will include conduit and suitable copper wiring between, utility disconnect, genset to ATS, and customer control panel. d) Contractor shall obtain any required permits and include costs in bid. e) Contractor shall configure generator controller and ATS for automatic switch operation. f) Each ATS must be installed in compliance with current local and national electric codes. 2) Lift Station Installation Locations: a) 94 Commons, 1423 N. St. Augustine Road: i) Power details: 480V, 3-phase, and 100A control panel main breaker. ii) Generator details: PDG 30kW diesel genset with DSE 7310 MKII controller b) Big Country Club, 3353 Plantation Drive: i) Power details: 208V, 3-phase, and 400A control panel main breaker. ii) Generator details: PDG 125kW diesel genset with DSE 7310 MKII controller. iii) ATS must be installed elevated to same height as control panel and generator since this location is subject to flooding. c) Boys and Girls Club, 3658 Lake Laurie Drive: i) Power details: 480V, 3 phase 480V, 3 phase, and 100A control panel main breaker. ii) Generator details: PDG 80kW diesel genset with DSE 7310 MKII controller. d) Cherry Creek #1, 3883 Staten Road: i) Power details: 480V, 3 phase, and 100A control panel main breaker. ii) Generator details: PDG 80kW diesel genset with DSE 7310 MKII controller. iii) This ATS must be installed elevated to same height as generator since this location is subject to flooding. e) Eastwind, 3113 Falling Leaf Lane: i) Power details: 240V, 3 phase, and 200A control panel main breaker. ii) Generator details: 60kW diesel genset with DSE 7310 MKII controller f) Hyde Park, 1509 Weaver Street: i) Power details: 230V, 1 phase, and 100A control panel main breaker. ii) Generator details: PDG 30kW diesel genset with DSE 7310 MKII controller. g) Mack Drive, 606 Howell Brook Drive: i) Power details: 240V, 3-phase, and 200A and control panel main breaker. ii) Generator details: Generac RD050 50kW diesel genset with Generac Evolution controller h) Ponderosa, 939 Ponderosa Drive: i) Power details: 240V, 3-phase, and 100A control panel main breaker. ii) Generator details: PDG 30kW diesel genset with DSE 7310 MKII controller