Specifications include, but are not limited to: Eight (8) 2500KVA Three Phase Pad-mounted Distribution, Dead Front, and Loop Feed transformers. The transformer shall be provided with six (6) 200 amp bushing wells, with replaceable studs, externally clamped. Gaskets shall be made of Nitrile, Corpreme or other approved material. Limiters shall be provided to prevent over compression of the gasket. High voltage leads lengths shall allow field replacement of bushing wells without the need to access through the top hand hole cover. Bushing well clamping rings shall be constructed of AISI Series 300 stainless steel, aluminum or other approved corrosion proof material. Clamping bolts and studs shall be constructed of stainless steel. Clamping studs shall be minimum 3/8 inch diameter. Nuts shall be AISI Type 316 stainless steel or silicon bronze. To minimize interference with installation of bushing inserts the clamping stud bolt length shall be such that a minimum number of threads extend beyond the clamping ring nuts.