Specifications include, but are not limited to: Annual Winter Maintenance (1 per year) Prior to scheduling the maintenance inspection, the Work Control Manager and the Energy Management Analyst must agree to the scheduled dates of service. Contact phone # 678-891-3891 Report in with the Customer Representative. Record and report abnormal conditions, measurements taken, etc. Review customer logs with the customer for operational problems and trends. Provide complete log of all operating parameters Leak check high side only Purge Replace flare drier and flare strainer to Turboguard purge. Check operation of float switch in purge tank. Verify the operation of the fill/drain cycle of Turboguard purge. Verify the operation of the purge check valves. Verify the operation of the foul gas outlet cage float valve. Verify the operation of the purge relief solenoid valve and pressure switch.