Specifications include, but are not limited to: A. Long Bed Skid Mounted (skid dimensions are not to exceed 48" wide x 96" long), High-Pressure 2-Stage Fire Pump (300-gallon capacity) B. Quantity: two (2) Skid Mounted High-Pressure 2-Stage Fire Pump C. Per the below specifications: 1. Minimum of 13 Horsepower (HP) Engine, 4-Cycle, Electric Start, High-Pressure 2-Stage Fire Pump 2. Flow rates at specified pressure: D. Maximum (Max) 230 Pounds per Square Inch (PSI). Max 105 Gallons per Minute (GPM) E. 97 GPM (367 liters per minute (lpm)) @ 100 PSI (6.9 BAR (unit of measure for pressure)) F. 80 GPM (303 lpm) @ 150 PSI (10.3 BAR) G. 58 GPM (202 lpm) @ 200 PSI (13.8 BAR) Including: A. (1) Welded 300-gallon storage tank made from high-density polyethylene plastic, baffled to National Fire Protection Association (NFPA) requirements B. Welded stainless steel manifold C. (1) 2-1/2" National Standard Thread (NST) Draft Suction D. (1) 2-1/2" NST Direct Fill E. (2) 1-1/2" NST Auxiliary Discharge F. (1) 1" Tank fill/ Recirculate G. (1) 1" gated pump-to-reel H. (1) Control Panel I. (1) Battery box (battery included)