Specifications include, but are not limited to: 1. Government Office Complex (Ernie Lee Magaha) - 221 Palafox Place The existing standby power system, consisting of an 80kW, 208Y/120V, 3-phase/4-wire generator, an ATS in the 221 Palafox building main electrical room, an ATS in the Artel Gallery and all associated feeders, shall be disconnected and removed. The existing standby power system will be replaced with a new 400kW, 480Y/277V, 3-phase/4-wire diesel generator. The generator shall be provided with a 48-hour sub-base fuel tank and High-Velocity Hurricane-Zone (HVHZ) aluminum enclosure. The new generator shall serve the entire service for 221 Palafox via an 800A, 480Y/277V, 4-Pole, NEMA 3R, service-rated, ATS. The existing service to Switchboard MDP shall be demolished. A new service shall extend from the existing FPL pad-mount transformer in the 221 Palafox parking lot to the new servicerated ATS. An 800A feeder shall extend from the new ATS to switchboard MDP. The main circuit breaker at MDP shall be adjusted to 840A and the neutral and ground shall be isolated within the switchboard. A second generator feeder shall extend from the new generator to a new 175A, 208Y/120V, 4-Pole, NEMA 1 ATS in the Artel Gallery main electrical room. Department of Juvenile Justice - 1800 St. Mary Street A new 800kW, 480Y/277V, 3-phase/4-wire diesel generator shall be provided to serve the entire service for the Department of Juvenile Justice. The new generator shall be provided with a 48-hour sub-base fuel tank, HVHZ enclosure, and elevated catwalk. Brownsville Community Center - 3200 West De Soto Street.