Specifications include, but are not limited to: • Provide and install a TROVE2M2 enclosure with and Altronix 12 VDC power supply, PD8 fused distribution board, 24 VDC power supply, ACM8 relay module and (3) 7AH batteries. • Provide and install (1) LNL-2220 intelligent controller and (2) LNL-1320-S3 dual reader expansion boards. • Connect the controller to the local COJ network switch and program in the provided IP address. • Provide and install access control hardware on (5) doors including the Front Employee Entry, and (4) interior doors. • Provide and install a mullion-mounted card reader, mullion-mounted emergency exit button, maglock, request to exit motion sensor and a door status switch for the Front Employee Entry. • Provide and install a card reader, door status switch, request to exit motion sensor and an electrified strike on each door for (4) Interior Doors • Provide and install low voltage access control cabling from each door to the Computer Room (head end install). • Provide and install surface mounted conduit, as needed, for the 1 perimeter doors. • Coordinate programming and testing with a City of Jacksonville representation to include testing doors for proper card reads and held open/forced open alarms.